DMP 714-8L-G 8-Zone Expander Module in 350 Enclosure

Part number / SKU
714-8L-G

$167.37

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The DMP 714-8L-G is a DMP 714-8 eight-zone expander supplied in a 350 enclosure. The 714 Series provides supervised zones for burglary and nonpowered fire devices on DMP XT30/XT50, XR150/XR550 and XF6 Series panels, connecting to the Keypad Bus or the LX-Bus.

The expander operates on 8.8 to 15.0 VDC and draws an average of 20 mA plus 1.6 mA per zone, with 2 mA per zone in alarm. Zones use 1k to 4.7k ohm end-of-line resistors on hardware Level E and higher, with an operating range of 650 to 2,100 ohms and a maximum line impedance of 100 ohms. TENS and ONES rotary switches set the starting address, and a data LED flashes on each poll. The 350 enclosure measures 17.50 x 13.50 x 3.50 in, includes a lock and key, has dual 1/2 and 3/4 in conduit knockouts on each side, and can be surface or flush mounted. The 714 Series is UL listed, including UL 864, and carries CSFM and FDNY approvals.

  • Best for: adding supervised burglary or nonpowered fire zones to DMP panels where a separate enclosure is needed.
  • System fit: DMP XT30/XT50, XR150/XR550 and XF6 Series panels (Keypad Bus or LX-Bus).
  • Important to know: UL commercial burglary needs the UL-listed enclosure with tamper; installation and programming should be done by a qualified alarm technician.

Why teams choose it

Built for secure sites

  • Eight supervised zones

    for burglary and nonpowered fire devices.

  • Own enclosure

    350 enclosure with lock and key and dual conduit knockouts.

  • Flexible addressing

    rotary switches on Keypad Bus or LX-Bus.

  • Fire and burglary listed

    UL 864 and UL 1610 series listings with CSFM and FDNY.

Specifications

Technical specifications

General
Brand DMP
Series 714 Series
Model 714-8L-G
Device Type Zone expander in enclosure
Zones 8 supervised zones (burglary and nonpowered fire)
EOL Resistor 1k to 4.7k ohm (hardware Level E and higher); 1k ohm on Level D or lower
Zone Operating Range 650 to 2,100 ohms; 100 ohm max line impedance
Addressing TENS and ONES rotary switches
Bus Keypad Bus or LX-Bus (jumper select)
Electrical
Operating Voltage 8.8 to 15.0 VDC
Zone Voltage 9.7 to 14.0 VDC
Current Draw 20 mA average plus 1.6 mA per zone; 2 mA per zone in alarm
Wire Gauge 18 or 22 AWG
Wire Length 1,000 ft max to bus; 2,500 ft max bus circuit
Physical
Enclosure Model 350, 17.50 x 13.50 x 3.50 in, lock and key
Knockouts Dual 1/2 and 3/4 in conduit knockouts each side
Mount Type Surface or flush
Note UL commercial burglary needs a UL listed enclosure with tamper
Listings and Approvals
Agency Approvals UL 365, 609, 864, 985, 1023, 1076, 1610; ULC Subject-C1023, ORD-C1076, S304; CSFM; FDNY