DMP · Intrusion & Alarm

DMP 734 Access Control Module for Keypad Bus or AX-Bus, 10 A Relay

Part number / SKU
734

$153.95

Special order· Lead time confirmed by our team after you order.

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The DMP 734 is a one-door access control module for DMP XT Series and XR Series panels. It connects to the panel Keypad Bus or AX-Bus, accepts a Wiegand or OSDP card reader, and switches the door lock with a 10 A Form C relay. Each module address covers one door and four expansion zones.

The module operates on 8.5 to 28.5 VDC from a 12 or 24 VDC supply, drawing 240 mA in standby and 260 mA in alarm including 200 mA for a proximity reader. Zones 1 to 3 are grounded 1k ohm zones for burglary or access control use, with zone 3 wirable as a bypass-only request to exit, and zone 4 is a non-powered Class B ungrounded fire zone. Status outputs for remote LED, remote annunciation and armed status are 100 mA switched ground. It measures 4.5 x 2.75 x 1.75 in, weighs 5.6 oz and is listed to UL 294 along with CSFM and FDNY.

OSDP needs 734 firmware Version 106 and Hardware Level 102. On XR550 panels using AX-Bus, the system supports up to 32 doors, expandable to 96.

  • Best for: adding card reader door control to DMP XT and XR intrusion systems.
  • System fit: DMP XT Series and XR Series panels; Wiegand and OSDP readers.
  • Important to know: if powered at 24 VDC, only another 734 at 24 VDC may be on KYPD OUT; installation should be done by a qualified access control technician.

Why teams choose it

Built for secure sites

  • Heavy-duty relay

    10 A Form C contacts at 12/24 VDC.

  • Reader choice

    Wiegand or OSDP readers.

  • Door inputs built in

    zones 2 and 3 can serve access control, including request to exit.

  • Access listed

    UL 294 with CSFM and FDNY.

Specifications

Technical specifications

General
Brand DMP
Model 734
Device Type Access control module
Doors 1 per module
Reader Interface Wiegand; OSDP (firmware Version 106, Hardware Level 102)
Zones 3 grounded zones (1k ohm EOL) plus 1 non-powered Class B ungrounded fire zone
Status Outputs LC, RA, AS: switched ground, 100 mA max each
Addressing DIP switches, addresses 1 to 16
Bus Keypad Bus or AX-Bus
Electrical
Operating Voltage 8.5 to 28.5 VDC (12 or 24 VDC supply)
Standby Current 240 mA (includes 200 mA reader)
Alarm Current 260 mA (includes 200 mA reader)
Relay Form C (SPDT), 10 A resistive at 12/24 VDC; relay draws 35 mA
Zone Output 750 mA max total
Wire Length Keypad Bus 500 ft (22 AWG) or 1,000 ft (18 AWG); 2,500 ft max per circuit
Physical
Dimensions 4.5 x 2.75 x 1.75 in (11.43 x 7 x 4.45 cm)
Weight 5.6 oz (0.16 kg)
Included 734 module, mounting base, three #6 x 1 in screws, three standoffs
Listings and Approvals
Agency Approvals UL 294, 365, 609, 864, 985, 1023, 1076, 1610; ULC S304, ORD-C1076, Subject-C1023, S545; CSFM; FDNY
FCC Part 15