Gamewell-FCI MS-7LOB Outdoor Double Action Conventional Manual Pull Station with SB-I/O Back Box
- Part number / SKU
- MS-7LOB
- Manual fire alarm pull station
- Conventional
- SB-I/O back box
- UL, FM, MEA, CSFM
Works with: Any UL Listed fire alarm control panel, SB-I/O indoor/outdoor back box (included), WP-10 back box (retrofit) Confirmed by the manufacturer
$108.99
Special order· Lead time confirmed by our team after you order.
- Warranty
- Manufacturer warranty
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
- 30-day returns
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Outdoor listed
listed by Gamewell-FCI for outdoor applications.
-
Fewer accidental pulls
double action operation needs two actions to activate.
-
Back box included
comes with the SB-I/O indoor/outdoor back box.
-
Wide temperature range
rated -30 to 150 F.
Specifications
Technical specifications
| General | |
|---|---|
| Brand | Gamewell-FCI |
| Series | MS-7 Series |
| Model | MS-7LOB |
| Device Type | Manual fire alarm pull station |
| Device Type Detail | Outdoor |
| Operation | Double action |
| Addressing | Conventional |
| Contact Rating | 0.25 A at 30 VAC/VDC (resistive) |
| Reset | Tumbler key lock for test and reset, keyed alike with Gamewell-FCI fire alarm control panels and pull stations |
| Pull Force | Meets ADA 5 lb maximum |
| Handle | Operating instructions and Braille engraved in the handle |
| Included | SB-I/O indoor/outdoor back box |
| Physical | |
| Mount Type | SB-I/O back box |
| Mount Type Detail | WP-10 back box in retrofit applications |
| Material | Lexan |
| Dimensions | 5 5/8 H x 4 1/4 W x 1 1/4 D in |
| Construction | Shock and vibration resistant |
| Environmental | |
| Operating Temperature | -30 to 150 F (-35 to 66 C) |
| Humidity | 85% plus or minus 5% at 86 plus or minus 3.6 F (30 plus or minus 2 C) |
| Listings and Approvals | |
| Agency Approvals | UL, FM, MEA, CSFM |
| Approval Details | UL S2465; FM 3023594; MEA FDNY 67-02-E Vol. VII; CSFM 7160-1703:0119, 7160-1703:0170, 7160-1703:0109 |
| Standards | UL 864, 9th Edition |