Honeywell · Fire Alarm

Honeywell Fire-Lite B200SR-WH Intelligent Sounder Base, 85 dBA, White

Part number / SKU
B200SR-WH
  • Intelligent sounder base
  • Addressable
  • Detector base, ceiling or wall
  • UL, ULC, FM, CSFM

Works with: System Sensor 200 Series addressable detector heads, B501BH Series sounder base installations (retrofit), Fire-Lite ES-200X control panel Confirmed by the manufacturer


$33.99

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The B200SR-WH is a white intelligent sounder base that mounts a 200 Series addressable detector head and adds a local sounder. The control panel can switch the sounder through the SLC, and a jumper selects ANSI Temporal 3 or continuous tone.

The sounder delivers more than 85 dBA minimum at 10 ft (24 V, continuous tone, UL reverberant room). It runs on an external 16 to 33 VDC supply drawing 500 uA maximum in standby and 35 mA maximum in alarm, with SLC operation at 15 to 32 VDC and 300 uA maximum standby. The 6.875 in base is 2.0 in high without the detector, takes wire up to 12 AWG, and is rated for 32 to 120 F and 10 to 93 percent RH. It fits existing B501BH Series sounder base installations.

  • Best for: addressable detector locations that need a local audible alarm, including existing B501BH Series sounder base installations.
  • System fit: System Sensor 200 Series addressable detector heads on a compatible addressable panel; external 24 VDC supply.
  • Important to know: installation and programming must be done by a qualified fire alarm technician in line with local code and the panel manufacturer's instructions.

Why teams choose it

Built for fire alarm systems

  • Local alarm

    more than 85 dBA minimum at 10 ft.

  • Two tones

    ANSI Temporal 3 or continuous, set by jumper.

  • Low standby draw

    500 uA maximum on the external supply, 300 uA on the SLC.

  • Listed base

    UL/ULC S1115, FM Approved, CSFM 7300-1653:0109.

Specifications

Technical specifications

General
Brand Fire-Lite (Honeywell), System Sensor design
Model B200SR-WH
Device Type Intelligent sounder base
Addressing Addressable
Addressing Detail With 200 Series detector head
Mount Type Detector base, ceiling or wall
Sound Output Greater than 85 dBA minimum at 10 ft, 24 V, continuous tone (UL reverberant room)
Tones ANSI Temporal 3 or continuous (jumper)
Head Lock Mechanical locking feature for the sensor head
Electrical
External Supply Voltage 16 to 33 VDC
External Supply Standby Current 500 uA maximum
Alarm Current 35 mA maximum
SLC Operating Voltage 15 to 32 VDC
SLC Standby Current 300 uA maximum
Wire Size Up to 12 AWG (2.5 mm2); terminals set for 14 AWG; Honeywell page states 12 to 24 AWG
Physical
Diameter 6.875 in (17.46 cm)
Height 2.0 in (5.08 cm) less sensor
Weight 0.50 lb (227 g)
Color White (WH)
Environmental
Operating Temperature 32 to 120 F (0 to 49 C)
Humidity 10 to 93 percent RH, non-condensing
Listings and Approvals
Standards Designed to meet or exceed UL 268 and UL 464 (installation manual)
Agency Approvals UL, ULC, FM, CSFM
Approval Details UL/ULC listed S1115; FM Approved; CSFM 7300-1653:0109, 7300-1653:0126, 7300-1653:0213, 7300-1653:0236