Kidde · Fire Alarm

Edwards 6830-3 Portable Fire Fighters Telephone Handset, Plug-In, Black

Part number / SKU
6830-3
  • Portable telephone handset, plug-in

$118.96

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Edwards 6830-3 is a black, plug-in portable telephone handset for Edwards fire fighters' telephone systems. It connects at fire fighters' telephone wall plate receptacles such as the Edwards 6833-4.

Each wall plate is driven by one signal module from the SIGA-CC1, SIGA-CC1S, SIGA-MCC1 or SIGA-MCC1S families (or their GSA versions), with a recommended maximum of five signal modules per telephone riser. Riser wiring is twisted, shielded, jacketed pair from 14 to 22 AWG, with a maximum line impedance of 50 ohms (25 ohms per line) and a 47 kohm end of line resistor on the last unit only. The equipment is rated for 32 to 120 °F (0 to 49 °C) and 93% RH noncondensing at 90 °F (32 °C).

  • Best for: fire fighters' telephone systems that use plug-in portable handsets at wall plate receptacles.
  • System fit: Edwards 6833-4 wall plate receptacle on a riser driven by SIGA-CC1 or SIGA-CC1S family signal modules.
  • Important to know: Edwards states that three-state telephones do not comply with UL 864 ninth edition; installation and programming must be done by a qualified fire alarm technician per local code.

Why teams choose it

Built for fire alarm systems

  • Plug-in use

    connects at fire fighters' telephone wall plate receptacles such as the 6833-4.

  • Signal module options

    each wall plate is driven by one SIGA-CC1, SIGA-CC1S, SIGA-MCC1 or SIGA-MCC1S family module.

  • Wide wire range

    riser accepts twisted, shielded pair from 14 to 22 AWG.

  • Color choice

    black handset; Edwards also lists a red portable handset, 6700-0061.

Specifications

Technical specifications

General
Brand Edwards
Model 6830-3
Device Type Portable telephone handset, plug-in
Color Black
Application Fire fighters' telephone
Companion Receptacle 6833-4 wall plate receptacle
Red Version 6700-0061
Electrical
Riser Cable Twisted, shielded, jacketed pair
Wire Gauge 14 to 22 AWG (2.08 to 0.33 mm²)
Max Line Impedance 50 ohms (25 ohms per line)
EOL Resistor 47 kohm, last unit only
Signal Modules One per wall plate; recommended max five per telephone riser
Physical
Wall Plate Size (6833-4) 4 1/2 in H x 2 3/4 in W x 1 1/4 in D (11.4 x 7.0 x 3.2 cm)
Wall Plate Box North American single gang, 2 1/2 in (64 mm) deep, not supplied
Environmental
Operating Temperature 32 to 120 °F (0 to 49 °C)
Humidity 93% RH, noncondensing at 90 °F (32 °C)
Listings and Approvals
Standards Edwards states three-state telephones do not comply with UL 864 ninth edition