Edwards BPS10A 10 A Remote Booster Power Supply, 4 NACs, 120 VAC
- Manufacturer part number
- BPS10A
- EhubAmerica SKU
- BPS10A-RLX
- Remote booster power supply
- 24 Vdc
- UL 864 9th ed. (UOXX); UL 636; UL 609; UL 294; UL 365; UL 1076; UL 1610; ULC-S527; ULC-S303; ULC-S304; C22.2 No. 205; CSFM
$407.30
Special order· Lead time confirmed by our team after you order.
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
- 30-day returns
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
More NAC power
10 A total at 24 Vdc across four supervised NACs, 3.0 A max each.
-
Synchronized appliances
synchronizes Genesis horns and strobes up to 10 boosters deep.
-
Flexible outputs
four Class B or two Class A NACs, or auxiliary outputs up to 8 A.
-
Wide listing set
UL 864 9th edition plus security and access control listings (UL 609, UL 1076, UL 294).
Specifications
Technical specifications
| General | |
|---|---|
| Brand | Edwards |
| Model | BPS10A |
| Device Type | Remote booster power supply |
| NACs | 4 independent, supervised |
| NAC Wiring | 4 Class B or 2 Class A, jumper selectable |
| Auxiliary Output | NACs configurable as auxiliary, plus dedicated 200 mA output; 8 A max auxiliary |
| Synchronization | Genesis horns and strobes, up to 10 boosters deep |
| Signal Rates | Continuous, 3-3-3 temporal, or follow panel NAC |
| Activation | 2 sense inputs, from panel NAC or Signature Series modules |
| Trouble Relay | 2 A at 30 Vdc; 16 s delay on AC failure or brownout |
| Module Space | Three two-gang Signature modules |
| Ordering Variants | BPS10AC (ULC), BPS10A/230 (220 V), BPS10CAA (California rate) |
| Electrical | |
| AC Input | 120 VAC, 50/60 Hz, 375 W (BPS10A/230 version for 220 to 240 VAC) |
| Operating Voltage | 24 Vdc |
| Output Current | 10 A total; 3.0 A max per NAC at 24 Vdc nominal |
| Sense Input Current | 3 mA at 12 Vdc; 6 mA at 24 Vdc |
| Supervisory Current | 70 mA |
| Battery Capacity | Up to 10 Ah in cabinet; up to 24 Ah in external cabinet (fire and security); up to 65 Ah (access control only) |
| Wire Size | 18 to 12 AWG |
| EOL Resistor | 15 kohm (UL listed EOL) |
| Physical | |
| Enclosure | Cabinet with battery compartment, module and tamper switch space; 3/4 in conduit knockouts |
| Weight | 13 lb (5.9 kg) |
| Environmental | |
| Operating Temperature | 32 to 120 °F (0 to 49 °C) |
| Humidity | 0 to 93% RH, noncondensing at 32 °C |
| Listings and Approvals | |
| Agency Approvals | UL 864 9th ed. (UOXX); UL 636; UL 609; UL 294; UL 365; UL 1076; UL 1610; ULC-S527; ULC-S303; ULC-S304; C22.2 No. 205; CSFM |