Kidde GSA-WTM Addressable Waterflow and Tamper Module, Two Class B Inputs

Part number / SKU
GSA-WTM
  • Waterflow and tamper module
  • Addressable
  • One-gang standard mount
  • 15.2 to 19.95 VDC
  • UL; ULC; CSFM; MEA

Works with: Signature loop controller, Kidde VS Series control panels, Kidde VM Series control panels, GSA-MP mounting plate, 27193-11 red one-gang surface box, 27193-16 white one-gang surface box and 1 more model Confirmed by the manufacturer


$67.17

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Kidde GSA-WTM is a two-circuit intelligent module for sprinkler monitoring on Kidde VS and VM series fire alarm systems with the Signature loop controller. Circuit 1 accepts Class B normally open waterflow alarm switches, and Circuit 2 accepts Class B normally open dry contact supervisory and tamper switches.

The waterflow circuit sends an alarm after its contact has been closed for about 16 seconds, and conditions on both circuits latch at the module. It runs on 15.2 to 19.95 VDC from the loop and draws 396 µA standby and 680 µA activated. Each input circuit allows 25 ohm per wire, 50 ohm per circuit and 0.1 µF, and terminals take 18 to 12 AWG wire with up to 4,000 ft to the end of line resistor.

It mounts in a 2-1/2 in deep one-gang box or a 1-1/2 in deep 4 in square box with a one-gang cover and a GSA-MP mounting plate. Red 27193-11 and white 27193-16 one-gang surface boxes and the MFC-A cabinet are available.

  • Best for: monitoring a sprinkler waterflow switch and a valve tamper switch with one addressable module.
  • System fit: Kidde VS and VM series intelligent fire alarm systems (Signature loop controller).
  • Important to know: both inputs are Class B normally open dry contacts and the module does not support 2-wire smoke detectors; installation and programming must be done by a qualified fire alarm technician per local code.

Why teams choose it

Built for fire alarm systems

  • Two inputs in one

    one waterflow alarm circuit and one supervisory or tamper circuit.

  • Built-in waterflow delay

    alarm is sent after the contact stays closed about 16 seconds.

  • Latched conditions

    alarm and supervisory states latch at the module.

  • Long input runs

    up to 4,000 ft to the end of line resistor on 12 to 18 AWG wire.

Specifications

Technical specifications

General
Brand Kidde
Model GSA-WTM
Device Type Waterflow and tamper module
Device Type Detail Addressable; supervisory
Addressing Addressable
Addressing Detail Signature loop controller
Type Code 49
Personality Codes 2 (circuit 1) and 4 (circuit 2), factory set
Inputs 2, Class B, normally open dry contact
Circuit 1 Waterflow alarm switches
Circuit 1 Delay Alarm after contact closed about 16 seconds
Circuit 2 Supervisory and tamper switches
Latching Both circuits latch at the module
Indicators Green LED flashes when polled; red LED flashes in alarm or active; both steady in standalone alarm
Mount Type One-gang standard mount
Compatible Systems Kidde VS and VM series
Electrical
Operating Voltage 15.2 to 19.95 VDC
Operating Voltage Detail 19 VDC nominal
Standby Current 396 µA
Activated Current 680 µA
Input Circuit Resistance 25 ohm per wire; 50 ohm per circuit max
Input Circuit Capacitance 0.1 µF per circuit max
Wire Size 18 to 12 AWG (0.75 to 2.5 mm²); 16 and 18 AWG preferred
Distance to End of Line Resistor 4,000 ft max
Two-Wire Smoke Detectors Not supported
Physical
Back Box 2-1/2 in (64 mm) deep one-gang box, or 1-1/2 in (38 mm) deep 4 in square box with one-gang cover
Mounting Plate GSA-MP plate
Surface Box 27193-11 (red) or 27193-16 (white), one-gang; MFC-A cabinet
Weight 0.4 lb
Environmental
Operating Temperature 32 to 120°F (0 to 49°C)
Storage Temperature -4 to 140°F (-20 to 60°C)
Humidity 0 to 93% RH
Listings and Approvals
Agency Approvals UL; ULC; CSFM; MEA