Edwards IO-SDC2 Dual Loop Controller Card for iO1000, 500 Addresses
- Part number / SKU
- IO-SDC2
- Dual loop controller card (expansion module)
- Addressable, Signature Series devices
- 24 VDC
$764.99
Special order· Lead time confirmed by our team after you order.
- Warranty
- Manufacturer warranty
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
- 30-day returns
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Two loops on one card
500 device addresses, 250 per loop.
-
Wiring choice
each loop can run Class A or Class B.
-
Low draw
45 mA standby and 70 mA alarm with fully loaded loops.
-
Isolation support
up to 64 isolator bases and modules per loop.
Specifications
Technical specifications
| General | |
|---|---|
| Brand | Edwards |
| Series | iO Series |
| Model | IO-SDC2 |
| Device Type | Dual loop controller card (expansion module) |
| Addressing | Addressable, Signature Series devices |
| Loops | 2 signaling line circuits |
| Loop Capacity | 125 detector and 125 module addresses per loop; 500 device addresses total |
| Panel Compatibility | iO1000 only |
| Isolators | 64 max per loop (isolator bases and modules combined) |
| Wiring | Class A or Class B |
| Electrical | |
| Operating Voltage | 24 VDC |
| Standby Current | 45 mA (fully loaded loops) |
| Alarm Current | 70 mA (fully loaded loops, excluding two-wire smoke modules) |
| Circuit Current | 0.5 A max |
| Loop Resistance | 66 ohms max |
| Loop Capacitance | 0.5 µF max |
| Communication Line Voltage | 20.6 V peak to peak max |
| Ground Fault Impedance | 0 to 5 kohms |
| Terminal Rating | 12 to 18 AWG (0.75 to 2.5 mm²) |
| Environmental | |
| Operating Temperature | 32 to 120°F (0 to 49°C) |
| Humidity | 0 to 93% RH, noncondensing at 90°F (32°C) |