Kidde · Fire Alarm

Edwards IO1000G iO1000 Intelligent Fire Alarm Control Panel, One 250-Point Loop, Gray

Manufacturer part number
IO1000G
EhubAmerica SKU
IO1000G-RLX
  • Intelligent fire alarm control panel
  • Addressable, Signature Series detectors and modules
  • 24 VDC
  • UL, FDNY

$925.84

Special order· Lead time confirmed by our team after you order.

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Edwards IO1000G is an iO1000 intelligent fire alarm control panel: a four-loop system with one 250-point Signature loop installed and a gray door. The loop supports 125 detectors and 125 modules, and loop controller cards add 250 points at a time up to 1,000 addresses. It has four notification appliance circuits, 32 input zones and a 4 x 20 character backlit LCD.

The panel runs on 120 VAC, 60 Hz (2.0 A max) and delivers 6.0 A of total NAC power, 2.5 A max per circuit, plus two 500 mA auxiliary outputs. It holds two 18 Ah batteries in the cabinet, with a 2.47 A max charging current, and has a Form C alarm relay, a trouble relay and a Form A supervisory relay, each rated 24 VDC at 1 A resistive.

Features include auto-programming, electronic addressing with automatic device mapping, CO detection support, SIGA-REL releasing modules, Genesis horn silence and UL 1971 strobe synchronization, and up to eight serial annunciators. Options include the SA-ETH Ethernet card, SA-DACT dialer, RZI16-2 conventional zone module, D16L-iO LED annunciators and SA-TRIM2 flush trim.

  • Best for: Signature Series installations that need room to grow, including retrofits that can use existing wiring.
  • System fit: Signature Series detectors and modules; IO-SDC1 and IO-SDC2 loop cards; R-Series remote annunciators.
  • Important to know: installation and programming must be done by a qualified fire alarm technician in line with local code and the panel documentation.

Why teams choose it

Built for fire alarm systems

  • Room to grow

    one 250-point loop installed, expandable to four loops and 1,000 addresses.

  • Notification power

    four NACs with 6.0 A total and 2.5 A per circuit.

  • Fast setup

    auto-programming with electronic addressing and automatic device mapping.

  • Releasing and CO

    supports SIGA-REL releasing modules and integrated CO detection.

Specifications

Technical specifications

General
Brand Edwards
Series iO Series
Model IO1000G
Device Type Intelligent fire alarm control panel
Addressing Addressable, Signature Series detectors and modules
Loops Four-loop system, one loop installed
Loop Capacity 250 addresses per loop (125 detectors and 125 modules); 1,000 addresses max
Isolators 64 max per loop
Notification Appliance Circuits 4 Class B or 2 Class A
Input Zones 32 max
Display 4 x 20 character backlit LCD
Remote Annunciators Up to 8 on RS-485, 4,000 ft (1,219 m) max data line
Door Gray door
Electrical
AC Input 120 VAC, 60 Hz, 2.0 A max
NAC Output 6.0 A total at 120 VAC, 60 Hz
Operating Voltage 24 VDC
NAC Current per Circuit 2.5 A max
Standby Current 172 mA (base panel)
Alarm Current 267 mA (base panel)
Aux Power 1 500 mA at 24 VDC, continuous; up to 1 A if total NAC power is reduced by 500 mA
Aux Power 2 500 mA at 24 VDC, resettable
Alarm Relay Form C, 24 VDC at 1 A resistive
Trouble Relay 24 VDC at 1 A resistive
Supervisory Relay Form A, 24 VDC at 1 A resistive
Battery Sealed lead acid, 24 VDC; up to two 18 Ah batteries in the cabinet
Battery Capacity 26 Ah max
Charging Current 2.47 A max
Terminal Rating 12 to 18 AWG (0.75 to 2.5 mm²)
Environmental
Operating Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing
Listings and Approvals
Agency Approvals UL, FDNY
Seismic Optional earthquake hardening with BC-1 EQ kit, Importance Factor 1.5