Edwards IO1000G iO1000 Intelligent Fire Alarm Control Panel, One 250-Point Loop, Gray
- Manufacturer part number
- IO1000G
- EhubAmerica SKU
- IO1000G-RLX
- Intelligent fire alarm control panel
- Addressable, Signature Series detectors and modules
- 24 VDC
- UL, FDNY
$925.84
Special order· Lead time confirmed by our team after you order.
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
- 30-day returns
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Room to grow
one 250-point loop installed, expandable to four loops and 1,000 addresses.
-
Notification power
four NACs with 6.0 A total and 2.5 A per circuit.
-
Fast setup
auto-programming with electronic addressing and automatic device mapping.
-
Releasing and CO
supports SIGA-REL releasing modules and integrated CO detection.
Specifications
Technical specifications
| General | |
|---|---|
| Brand | Edwards |
| Series | iO Series |
| Model | IO1000G |
| Device Type | Intelligent fire alarm control panel |
| Addressing | Addressable, Signature Series detectors and modules |
| Loops | Four-loop system, one loop installed |
| Loop Capacity | 250 addresses per loop (125 detectors and 125 modules); 1,000 addresses max |
| Isolators | 64 max per loop |
| Notification Appliance Circuits | 4 Class B or 2 Class A |
| Input Zones | 32 max |
| Display | 4 x 20 character backlit LCD |
| Remote Annunciators | Up to 8 on RS-485, 4,000 ft (1,219 m) max data line |
| Door | Gray door |
| Electrical | |
| AC Input | 120 VAC, 60 Hz, 2.0 A max |
| NAC Output | 6.0 A total at 120 VAC, 60 Hz |
| Operating Voltage | 24 VDC |
| NAC Current per Circuit | 2.5 A max |
| Standby Current | 172 mA (base panel) |
| Alarm Current | 267 mA (base panel) |
| Aux Power 1 | 500 mA at 24 VDC, continuous; up to 1 A if total NAC power is reduced by 500 mA |
| Aux Power 2 | 500 mA at 24 VDC, resettable |
| Alarm Relay | Form C, 24 VDC at 1 A resistive |
| Trouble Relay | 24 VDC at 1 A resistive |
| Supervisory Relay | Form A, 24 VDC at 1 A resistive |
| Battery | Sealed lead acid, 24 VDC; up to two 18 Ah batteries in the cabinet |
| Battery Capacity | 26 Ah max |
| Charging Current | 2.47 A max |
| Terminal Rating | 12 to 18 AWG (0.75 to 2.5 mm²) |
| Environmental | |
| Operating Temperature | 32 to 120°F (0 to 49°C) |
| Humidity | 0 to 93% RH, noncondensing |
| Listings and Approvals | |
| Agency Approvals | UL, FDNY |
| Seismic | Optional earthquake hardening with BC-1 EQ kit, Importance Factor 1.5 |