Kidde · Fire Alarm

Edwards SIGA-CT1 Signature Series Single Input Module, One-Gang

Part number / SKU
SIGA-CT1
  • Single input module
  • Addressable, one module address, set electronically
  • Standard mount, one-gang box
  • 15.2 to 19.95 Vdc (19 Vdc nominal)
  • UL, ULC, MEA, CSFM

$53.99

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Edwards SIGA-CT1 is a Signature Series intelligent analog addressable single input module. It connects one Class B normally open dry contact initiating device circuit for alarm, supervisory or monitor duty, and its function is set by a personality code downloaded from the Signature loop controller.

Four personality codes cover latching alarm for pull stations and heat detectors, delayed latching alarm for waterflow switches, non-latching monitor for fans, dampers and doors, and latching supervisory for tamper switches. The module draws 250 µA in standby and 400 µA when activated on a 15.2 to 19.95 Vdc data line, uses one module address, and accepts #12 to #18 AWG wire with a 47 kΩ end-of-line resistor. It mounts in a 2-1/2 in deep one-gang box or a 1-1/2 in deep 4 in square box with a one-gang cover and SIGA-MP plate.

  • Best for: connecting pull stations, heat detectors, waterflow and tamper switches and other dry contacts to a Signature loop.
  • System fit: Edwards Signature Loop Controller on EST3, EST3X and iO Series control panels.
  • Important to know: installation and programming must be done by a qualified fire alarm technician in line with local code.

Why teams choose it

Built for fire alarm systems

  • Four input modes

    latching alarm, delayed latching waterflow alarm, non-latching monitor or latching supervisory.

  • Waterflow retard

    code 2 sends the alarm after the contact stays closed for about 16 seconds.

  • Long input runs

    up to 4,000 ft to the end-of-line resistor with #18 AWG wire.

  • Ground fault by address

    ground faults are detected down to the device level.

Specifications

Technical specifications

General
Brand Edwards
Model SIGA-CT1
Series Signature Series
Device Type Single input module
Addressing Addressable, one module address, set electronically
Mount Type Standard mount, one-gang box
Input Circuit One Class B normally open dry contact IDC
Type Code 48 (factory set), four sub-types
Personality Codes 1 (N.O. alarm, latching); 2 (N.O. alarm, delayed latching for waterflow, about 16 s); 3 (N.O. active, non-latching); 4 (N.O. active, latching, supervisory and tamper)
Indicators Green LED flashes when polled; red LED flashes in alarm or active
Electrical
Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)
Standby Current 250 µA
Activated Current 400 µA
EOL Resistor 47 kΩ
Circuit Output 10 Vdc max. at 350 µA
Wire Resistance 50 Ω max. per circuit (25 Ω per wire)
Wire Capacitance 0.1 µF max. per circuit
Distance to EOLR 4,000 ft (1,219 m) max. with #18 AWG
Wire Size #12 to #18 AWG (2.5 to 0.75 mm²)
Physical
Construction High impact engineering polymer
Mounting 2-1/2 in (64 mm) deep one-gang box; 1-1/2 in (38 mm) deep 4 in square box with one-gang cover and SIGA-MP plate
Weight 0.4 lb (0.15 kg)
Environmental
Operating Temperature 32 to 120°F (0 to 49°C)
Storage Temperature -4 to 140°F (-20 to 60°C)
Humidity 0 to 93% RH
Listings and Approvals
Agency Approvals UL, ULC, MEA, CSFM