Kidde · Fire Alarm

Edwards SIGA-RM1 Signature Series Riser Monitor Module, Standard Mount

Part number / SKU
SIGA-RM1
  • Riser monitor module
  • Addressable, one module address, set electronically
  • Standard mount, two-gang box
  • 15.2 to 19.95 Vdc
  • UL, ULC, MEA, CSFM

$99.00

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Edwards SIGA-RM1 is a Signature Series intelligent analog addressable riser monitor module. It monitors 12 and 24 Vdc circuits, 25 and 70 Vac audio circuits and telephone risers, and reports a trouble to the panel when riser voltage drops below about 25% of the riser input.

Personality code 23, the factory default, monitors 70 Vac, 25 Vac, 24 Vdc and 12 Vdc risers, with a hardware jumper set for 70 Vac or for 25 Vac/24 Vdc/12 Vdc. Code 24 monitors a telephone riser with a user-definable trouble delay of 5 to 75 seconds, 15 seconds by default. The module uses one module address on a 15.2 to 19.95 Vdc data line and accepts #12 to #18 AWG wire.

It mounts in a 2-1/2 in deep two-gang box or a 1-1/2 in deep 4 in square box with a two-gang cover and SIGA-MP plates. The SIGA-MRM1 is the UIO plug-in version.

  • Best for: supervising notification power, audio evacuation and firefighter telephone risers on Signature loop systems.
  • System fit: Edwards Signature Loop Controller on EST3, EST3X and iO Series control panels.
  • Important to know: installation and programming must be done by a qualified fire alarm technician in line with local code.

Why teams choose it

Built for fire alarm systems

  • Five riser types

    12 Vdc, 24 Vdc, 25 Vac, 70 Vac and telephone riser monitoring.

  • Loss-of-signal trouble

    reports trouble when riser voltage drops to about 25% of the riser input.

  • Adjustable telephone delay

    trouble delay settable from 5 to 75 seconds.

  • Light riser loading

    10 mA input current on 12, 24, 25 and 70 V risers.

Specifications

Technical specifications

General
Brand Edwards
Model SIGA-RM1
Series Signature Series
Device Type Riser monitor module
Addressing Addressable, one module address, set electronically
Mount Type Standard mount, two-gang box
Personality Codes 23 (riser monitor, factory default); 24 (telephone riser monitor)
Trouble Threshold Approximately 25% of riser input
Telephone Trouble Delay 5 to 75 s, 15 s default
Circuit Class Riser Style 4 (Class B); data Style 4 (Class B) or Style 6 (Class A)
Indicators Green LED flashes when polled; red LED flashes in alarm or active
Electrical
Operating Voltage 15.2 to 19.95 Vdc
Input Current 12/24 Vdc Riser 10 mA dc
Input Current 25/70 Vac Riser 10 mA rms
Input Current Telephone 20 mA dc at 24 Vdc
Riser Loading 70 Vac Z > 11 kΩ; 25 Vac Z > 1 kΩ; 24 Vdc R > 2.4 kΩ; 12 Vdc R > 1.2 kΩ; telephone R and Z > 1.2 kΩ
Wire Size #12 to #18 AWG (2.5 to 0.75 mm²)
Physical
Construction High impact engineering polymer
Mounting 2-1/2 in (64 mm) deep two-gang box; 1-1/2 in (38 mm) deep 4 in square box with two-gang cover and SIGA-MP plates
Weight 0.5 lb
Environmental
Operating Temperature 32 to 120°F (0 to 49°C)
Storage Temperature -4 to 140°F (-20 to 60°C)
Humidity 0 to 93% RH
Listings and Approvals
Agency Approvals UL, ULC, MEA, CSFM
FM Approval Scope Monitoring of 12 and 24 Vdc circuits only