Notifier FCM-1-REL FlashScan Addressable Releasing Control Module
- Part number / SKU
- FCM-1-REL
- Releasing control module
- Addressable
- Standard 4 in junction box
- 15 to 32 VDC
- UL, ULC, FM, CSFM
Works with: NFS2-3030 (v14.0 and later), NFS2-640 (v12.0 and later), NFS-320 (v12.0 and later), CB500 control module barrier, Solenoids per Notifier Device Compatibility Document PN 15378 Confirmed by the manufacturer
In stock
- Warranty
- Manufacturer warranty
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
- 30-day returns
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Redundant release protocol
arm and confirm signal pairs within a 3-second window before release.
-
Supervised solenoid circuit
solenoid power runs through the module and reports open or short conditions.
-
Flexible solenoid load
drives one 24 VDC solenoid or two 12 VDC solenoids in series, up to 2 A.
-
Supply monitoring
watches the external 24 VDC supply voltage.
Specifications
Technical specifications
| General | |
|---|---|
| Brand | Notifier |
| Model | FCM-1-REL |
| Device Type | Releasing control module |
| Device Type Detail | Addressable |
| Addressing | Addressable |
| Addressing Detail | Rotary address switches |
| Protocol | FlashScan |
| Wiring Class | Class A or Class B configurable |
| Release Logic | Arm signal pair then confirmation pair within 3 seconds; automatic reset if not confirmed |
| Solenoid Load | One 24 VDC solenoid or two 12 VDC solenoids in series |
| Indicators | Panel-controlled status LED |
| Electrical | |
| Operating Voltage | 15 to 32 VDC |
| SLC Average Current | 700 µA max at 24 VDC (one communication every 5 seconds, LED enabled) |
| SLC Activation Current | 9.0 mA max (LED on) |
| Loop Impedance | 40 ohm max |
| External Supply | 24 VDC nominal; 2.3 VDC max line loss supply to module plus module to solenoid |
| External Supply Current | 6.4 mA standby; 10 mA activation |
| Minimum Solenoid Voltage | 18 VDC at solenoid |
| Maximum Solenoid Current | 2 A |
| Solenoid Supervision | 3.3 V, 30 mA normal current |
| Physical | |
| Dimensions | 4.675 in H x 4.275 in W x 1.400 in D (11.87 x 10.86 x 3.56 cm) |
| Mount Type | Standard 4 in junction box |
| Mount Type Detail | 10.16 cm |
| Weight | 5.5 oz (156 g) |
| Environmental | |
| Operating Temperature | 14°F to 140°F (-10°C to 60°C) |
| Relative Humidity | 10% to 95% non-condensing |
| Listings and Approvals | |
| Agency Approvals | UL, ULC, FM, CSFM |
| Approval Details | UL Listed S635; ULC listed as FCM-1-RELA; FM Approved; CSFM 7300-0028:249 |