Notifier HON-CGW-MBB CLSS Gateway with Enclosure

Part number / SKU
HON-CGW-MBB
  • CLSS Gateway with enclosure
  • 12 to 32 VDC
  • ETL, CSFM, FDNY

Works with: NFS2-640, NFS-320, NFS2-3030, CCM-ATT-HON cellular module, CCM-VZ-HON cellular module, CELL-ANT3DB external antenna and 1 more model Confirmed by the manufacturer


$396.04

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Notifier HON-CGW-MBB is the CLSS Gateway with enclosure. It reads the connected device system inventory from one Honeywell fire alarm control panel or a network of panels and sends it to the CLSS Cloud, and with the optional cellular module and feature activation it also works as a fire alarm communicator to a central station.

The gateway runs on 12 to 32 VDC from the panel or an external source, drawing 0.1 A typical and 0.25 A peak at 24 V. It connects to the cloud over wireless or wired connection, uses Bluetooth mobile pairing for configuration and control, and is rated for 14°F to 140°F. The enclosure measures 10.25 x 8 x 3.75 in and weighs 1.6 lb.

Optional CCM-ATT-HON (AT&T) and CCM-VZ-HON (Verizon) cellular modules add a cellular path, and the CELL-ANT3DB antenna with the WA7626-CA adapter are both required for an external antenna. BACnet, Modbus, NFN and Connected Gateway are available as activation add-ons.

  • Best for: connecting Honeywell fire alarm panels to the CLSS Cloud for inventory and remote access, and central station communication with a cellular module.
  • System fit: Honeywell fire alarm control panels, standalone, networked or standalone with Digital Voice Control; FDNY COA lists NFS2-640, NFS-320 and NFS2-3030.
  • Important to know: central station reporting needs the optional cellular module and feature activation; installation and programming must be done by a qualified fire alarm technician in line with local code and the panel manufacturer's instructions.

Why teams choose it

Built for fire alarm systems

  • Cloud connection

    sends panel system inventory to the CLSS Cloud.

  • Communicator option

    acts as a fire alarm communicator with a CCM-ATT-HON or CCM-VZ-HON cellular module.

  • Low power

    0.1 A typical at 24 V, powered from the panel or an external 12 to 32 VDC source.

  • Protocol add-ons

    BACnet, Modbus, NFN and Connected Gateway available as activations.

Specifications

Technical specifications

General
Brand Notifier
Model HON-CGW-MBB
Device Type CLSS Gateway with enclosure
Function Sends panel inventory to CLSS Cloud; fire alarm communicator with cellular module
Panel Connection Standalone panel, networked panels, or standalone with Digital Voice Control
Cloud Connection Wireless or wired
Setup Bluetooth mobile pairing for configuration and control
Add-On Activations BACnet, Modbus, NFN, Connected Gateway
Electrical
Operating Voltage 12 to 32 VDC
Operating Voltage Detail From the FACP or an external source
Typical Current 0.1 A at 24 V (wireless connection)
Peak Current 0.25 A at 24 V
Physical
Enclosure Dimensions 10.25 in L x 8 in W x 3.75 in D (260.03 x 203.2 x 95.25 mm)
Weight 1.6 lb (0.73 kg)
Environmental
Operating Temperature 14°F to 140°F (-10°C to 60°C)
Relative Humidity 1% to 94% non-condensing
Wireless
Wireless Frequency 2.4 GHz and 5 GHz Wi-Fi
2.4 GHz TX Power 802.11b 17.5 dBm; 11g 15 dBm; 11n 15 dBm; 11ac 14 dBm (20 MHz), ±2.0 dB
5 GHz TX Power 11a 15 dBm; 11n 15 dBm; 11ac 14 dBm (20 MHz), 13 dBm (40 MHz), 12 dBm (80 MHz), ±2.0 dB
Cellular Optional CCM-ATT-HON (AT&T) or CCM-VZ-HON (Verizon) module
FCC ID PV3CGWMBB
Listings and Approvals
Agency Approvals ETL, CSFM, FDNY
Approval Details ETL 104270338NYM-001; CSFM 7300-1637:0504; FDNY COA# 2020-TMCOAP-000121-AMND (NFS2-640, NFS-320); FDNY COA# 2020-TMCOAP-000122-AMND (NFS2-3030)