Tycon · Power Supplies & UPS

Tycon TP-BC24-300 210W Smart Battery Charger 24VDC AGM/GEL/WET

EhubAmerica SKU
TP-BC24-300

$313.76

Special order· Lead time confirmed by our team after you order.

Warranty
Manufacturer warranty
Request a quote

Need project or contract pricing?

Request project pricing

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

PRODUCT OVERVIEW

Tycon TP-BC24-300 is a 210W smart battery charger designed for 24VDC AGM, GEL, and flooded (WET) lead-acid batteries. It provides intelligent multi-stage charging for compatible battery systems.

PRODUCT TYPE

Batteries

KEY FEATURES

• Genuine Tycon Power smart battery charger
• 210W charging capacity
• Designed for 24VDC battery systems
• Compatible with AGM, GEL, and flooded (WET) lead-acid batteries
• Intelligent multi-stage charging technology
• OEM Tycon Power accessory

TECHNICAL SPECIFICATIONS

• Brand: Tycon Power
• Model: TP-BC24-300
• Product Type: Smart Battery Charger
• Output Power: 210W
• Battery System Voltage: 24VDC
• Compatible Battery Types: AGM, GEL, Flooded (WET) Lead-Acid

Specifications

Technical specifications

General
Product Line TP-BC series
Model TP-BC24-300
Brand Tycon
Type Smart Battery Charger
Total Power Output 210W
Physical
Dimensions (L×W×H) 250 × 185 × 55mm (9.8 × 7.3 × 2.2")
Weight 2.4kg (5.2lb)
Power & Electrical
Nominal Battery Voltage 24VDC
Load Output Voltage 12VDC (Regulated)
Load Output Current (Min) 1A
Load Output Current (Max) 8A
Suggested Max Load ~5A (120W)
Battery Charge Max Current 7.5A (with zero load); 3.75A (with 5A load)
Battery Charger Voltage (WET) Equalize 28.8V, Float 26.4V
Battery Charger Voltage (GEL) Equalize 28.4V, Float 27V
Overdischarge Protection Load off at 21.5V / Load on at 25.2V
Load Regulation 5%
Line Regulation / Ripple 1%
Noise 2%
Efficiency (Minimum) 75%
Self Consumption <5W
Load and Battery Connections Screw Wire Terminal, 10 AWG maximum
Environmental
Operating Temperature Range Wide temperature operation
Compatibility
Compatible Battery Types GEL, AGM, WET
Optional Solar Panel Compatible with solar panel and solar charge controller
Optional Wind Power Compatible with Wind Turbine
General (Protection & Features)
Protections Short circuit, overvoltage, overcurrent, reverse battery
Load Control Automatic load disconnect to prevent overdischarge; automatic recovery
AC to Battery Switchover Seamless
Power Failure Recovery Automatic
Front Panel Indicators LEDs for Load Output, Charging Condition, and AC Power Condition status
Compatibility (Standards)
EMC Standards FCC Class A, NE55022 Class A
Safety Standards UL1950, CSA