Altronix · Power Supplies & UPS
Altronix AL400ULX 12/24VDC 4A Power Supply/Charger, BC300 Enclosure
- Part number / SKU
- AL400ULX
Works with: BC300 enclosure (included), Sealed lead acid or gel standby batteries Confirmed by the manufacturer
Special order· Lead time confirmed by our team after you order.
Need 5 or more? Request volume pricing
- (305) 357-6575
- 100K+ orders shipped
- 30-day returns
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for reliable networks
-
Selectable output
12VDC at 4 A or 24VDC at 3 A, Class 2 power-limited.
-
Battery backup
0.7 A charger with zero-drop switchover on AC failure.
-
Broad listings
UL 294, UL 603, UL 1481 and UL 1069, plus CSFM, MEA and FM.
-
Supervised
Form C contacts for AC fail, low battery and battery presence.
Specifications
Technical specifications
| Product identifiers | |
|---|---|
| SKU | AL400ULX |
| General | |
| Brand | Altronix |
| Model | AL400ULX |
| Device Type | Power supply/charger in enclosure |
| Output | 1 output, Class 2 rated, power-limited; filtered and electronically regulated |
| Protection | Short circuit and thermal overload |
| Battery Charger | Sealed lead acid or gel; automatic switchover on AC failure, zero voltage drop |
| Supervision | AC fail, low battery and battery presence (Form C contacts) |
| AC Fail Report Delay | 30 seconds (factory) or 6 hours, selectable |
| Indicators | AC input, DC output and battery LEDs |
| Electrical | |
| Input | 115VAC, 60 Hz, 3.5 A |
| Input Fuse | 3.5 A / 250V |
| System AC Input Requirement | 402.5 VA |
| Operating Voltage | 12VDC or 24VDC, selectable |
| Output Current | 4 A at 12VDC; 3 A at 24VDC |
| Burglar Alarm Voltage Range | 11.5 to 13 VDC (12V); 23 to 26 VDC (24V) |
| Maximum Charge Current | 0.7 A |
| Physical | |
| Enclosure | BC300, wall mount, indoor |
| Dimensions | 12.5 W x 13 H x 3.25 D in (317.5 x 330.2 x 82.6 mm) |
| Knockouts | 1/2 in and 3/4 in combination |
| Weight | Approx. 6.95 lb (3.15 kg) |
| Environmental | |
| Operating Temperature | 32 to 120 F (0 to 49 C) |
| Storage Temperature | -4 to 158 F (-20 to 70 C) |
| Relative Humidity | 85 percent +/- 5 percent |
| Heat Output | Approx. 25 BTU/hr at 12VDC; 37 BTU/hr at 24VDC |
| Listings and Approvals | |
| Agency Approvals | UL 294 (Access Control System Units); UL 603 (Power Supplies for Burglar Alarm Systems); UL 1481 (Power Supplies for Fire Protective Signaling Systems); UL 1069 (Hospital Signaling and Nurse Call Equipment); cUL to CSA C22.2 No. 205-M1983; ULC-S318-96; CSFM Approved (file 1335-0100); MEA Approved; FM Approved |
| Standards | NFPA 72 compliant |