Farenhyt · Fire Alarm

Farenhyt IDP-PHOTO-W Addressable Photoelectric Smoke Detector, White

Part number / SKU
IDP-PHOTO-W
  • Plug-in smoke detector head
  • Photoelectric
  • Addressable
  • Plug-in head
  • 15 to 32 VDC

Works with: IFP-2100 / IFP-2100ECS / RFP-2100 FACP, IFP-2000 / IFP-2000ECS / RPS-2000 FACP, IFP-1000 / IFP-1000ECS FACP, IFP-300 / IFP-300ECS FACP, IFP-100 / IFP-100ECS FACP, IFP-75 FACP and 13 more models Confirmed by the manufacturer


$68.99

Special order· Lead time confirmed by our team after you order.

Request a quote

Need project or contract pricing?

Request project pricing
  • Help in English, Spanish and Portuguese

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Farenhyt IDP-PHOTO-W is an intelligent, plug-in photoelectric smoke detector with integral communication for Farenhyt Series fire alarm control panels. Sensitivity is programmed in the panel software and is continuously monitored and reported to the panel, and the detector signals when maintenance is required.

It operates on 15 to 32 VDC and draws 300 uA in standby and alarm on the two-wire SLC. Rotary decimal address switches set the point address, dual LEDs give 360 degree visibility, and an external magnet activates the built-in functional test switch. The low-profile head is listed for duct applications at air velocities of 0 to 4000 fpm and installs 2.0 in high and 4.1 in in diameter on a B501 base.

The head plugs into B210LP, B501, B224BI isolator, B224RB relay or B200SR sounder bases. Optional accessories include the RA100Z remote LED annunciator, the XR2B removal tool and the M02-04-01 test magnet.

  • Best for: point smoke detection on Farenhyt IFP Series addressable fire alarm systems, including duct applications.
  • System fit: Farenhyt IFP-50, IFP-75, IFP-100, IFP-300, IFP-1000, IFP-2000 and IFP-2100 panels; B210LP, B501, B224BI, B224RB and B200SR bases.
  • Important to know: installation and programming must be done by a qualified fire alarm technician per local code.

Why teams choose it

Built for fire alarm systems

  • Panel-set sensitivity

    programmed from the panel and continuously monitored and reported.

  • Exact point ID

    rotary decimal address switches identify each detector location.

  • 360 degree status

    dual LEDs are visible from any direction.

  • Duct capable

    listed for duct applications at 0 to 4000 fpm air velocity.

Specifications

Technical specifications

Ask about a spec
Product identifiers
SKUIDP-PHOTO-W
General
Brand Farenhyt (Honeywell)
Model IDP-PHOTO-W
Device Type Plug-in smoke detector head
Device Type Detail Intelligent
Detection Type Photoelectric
Addressing Addressable
Addressing Detail Rotary decimal address switches
Communication Analog, two-wire SLC
Mount Type Plug-in head
Mount Type Detail For B210LP, B501, B224BI, B224RB or B200SR bases
Sensitivity Programmable from the FACP; continuously monitored and reported
Indicators Dual LEDs, 360 degree visibility
Test Built-in functional test switch, external magnet; remote test from the panel
Air Velocity 0 to 4000 fpm (0 to 20 m/s), suitable for ducts
Color White
Electrical
Operating Voltage 15 to 32 VDC
SLC Standby and Alarm Current 300 uA
Physical
Height 2.0 in (5.08 cm) less sensor
Diameter 4.1 in (10.4 cm) installed in B501 base
Housing Age resistant polymer, low profile
Insect Screen Hole Size 0.016 in (0.41 mm) nominal
Environmental
Operating Temperature 32 to 120 F (0 to 49 C)
Humidity 10 to 93 percent, non-condensing
Listings and Approvals
Agency Approvals UL S6173; FM Approved; CSFM 7272-0559:0512; MEA 225-02-E Vol. V

Security projects · South Florida

Planning a fire alarm, access or camera project?

Send the site details and our team helps with product selection, a site survey and a project quote.

Start a project request