Gamewell-FCI ATD-L3 Velociti Series 3 Addressable 135F Fixed Temperature Heat Sensor
- Part number / SKU
- ATD-L3
- Intelligent thermal sensor
- Fixed temperature, 135 F, 57 C
- Addressable, Velociti protocol
- Plug-in head
- 15 to 32 VDC
Works with: E3 Series panels (Velociti and CLIP), S3 Series panels (Velociti and CLIP), GWF-7075 panel (Velociti only), B501 4 in flangeless base, B300-6 6 in flanged base, B200SR-WH sounder base and 8 more models Confirmed by the manufacturer
Special order· Lead time confirmed by our team after you order.
- Warranty
- Manufacturer warranty
Free Economy shipping available at checkout
Need 5 or more? Request volume pricing
- (305) 357-6575
- 100K+ orders shipped
- 30-day returns
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Fixed temperature
alarms at 135 F (57 C).
-
Low standby load
200 uA at 24 VDC.
-
Wide operating range
rated -4 to 100 F.
-
Listed device
UL S2332, FM 3023594, CSFM and MEA FDNY.
Specifications
Technical specifications
| Product identifiers | |
|---|---|
| SKU | ATD-L3 |
| General | |
| Brand | Gamewell-FCI |
| Series | Velociti Series 3 |
| Model | ATD-L3 |
| Device Type | Intelligent thermal sensor |
| Device Type Detail | Heat |
| Detection Type | Fixed temperature, 135 F, 57 C |
| Addressing | Addressable, Velociti protocol |
| Addressing Detail | Rotary address switches 01 to 159 |
| Indicators | Dual LEDs for 360 degree visibility |
| Test Method | Built-in functional test switch activated by an external magnet |
| Electrical | |
| Operating Voltage | 15 to 32 VDC |
| Standby Current | 200 uA at 24 VDC (one communication every 5 seconds, green LED enabled) |
| Alarm Current | 2 mA max at 24 VDC (one communication every 5 seconds, red LED enabled) |
| Maximum Current | 4.5 mA at 24 VDC (one communication every 5 seconds, amber LED enabled) |
| Physical | |
| Height | 2.0 in (51 mm) installed in B300-6 base |
| Diameter | 6.1 in installed in B300-6 base; 4 in (10.2 cm) installed in B501 base |
| Weight | 3.4 oz |
| Color | Bright white |
| Mount Type | Plug-in head |
| Mount Type Detail | For B501 or B300-6 base; optional sounder, relay and isolator bases |
| Environmental | |
| Operating Temperature | -4 to 100 F (-20 to 38 C) |
| Humidity | 10% to 93% non-condensing |
| Listings and Approvals | |
| Agency Approvals | UL S2332; FM 3023594; MEA FDNY 219-02-E Vol. VI; CSFM 7270-1703-0502 |
| Standards | UL 268 |