Macurco · Fire Alarm

Macurco DVP-120M Detection and Ventilation Control Panel, 12 Analog Inputs, Modbus

Part number / SKU
DVP-120M
  • Detection and ventilation panel
  • ETL Listed to UL 508A

Works with: Macurco 6-Series gas detectors (via MRS-485 adapter), MRS-485 Modbus adapter, DVP-485 Modbus adapter, Macurco 4 to 20 mA gas transducers, Macurco GD-6 combustible gas detector Confirmed by the manufacturer


$1,866.99

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing
  • Help in English, Spanish and Portuguese

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Macurco DVP-120M is a detection and ventilation control panel for gas detection systems. It accepts up to 12 analog 4 to 20 mA gas sensors and is the Modbus version of the DVP-120, adding up to 87 addressable sensors on three RS-485 channels for up to 99 detectors in total.

Three SPDT (Form C) relays rated 10 A resistive at 120/240 VAC (pilot duty) control fans or alarms, and two 24 VDC, 250 mA drivers run an external horn and strobe. The panel runs on 90 to 250 VAC, 47 to 63 Hz, has a backlit 2 x 16 character LCD and a 90 dBA internal buzzer, and sits in a lockable NEMA 1 enclosure of 10.5 x 12.5 x 2 in. It is ETL listed to UL 508A and CAN/CSA C22.2 No. 14-13.

It works with Macurco transducers that have 4 to 20 mA outputs and, through the MRS-485 adapter, with Macurco 6-Series detectors on Modbus. The panel supports eight standard sensor types (CO, NO2, EX, NH3, H2S, REF, CO2, O2) and 21 custom types.

  • Best for: gas detection systems that switch ventilation fans and alarms from sensor readings.
  • System fit: Macurco 6-Series detectors via MRS-485 adapters; Macurco 4 to 20 mA transducers.
  • Important to know: this is a gas detection and ventilation controller, not a fire alarm control panel; relays are for pilot duty only.

Why teams choose it

Built for fire alarm systems

  • Mixed sensor inputs

    12 analog 4 to 20 mA channels plus up to 87 Modbus sensors.

  • Fan and alarm control

    three Form C relays rated 10 A resistive at 120/240 VAC.

  • Local alerts

    90 dBA buzzer and two 24 VDC horn/strobe drivers.

  • Wide power input

    90 to 250 VAC, 47 to 63 Hz.

Specifications

Technical specifications

Ask about a spec
Product identifiers
SKUDVP-120M
General
Brand Macurco
Model DVP-120M
Device Type Detection and ventilation panel
Device Type Detail Detection and ventilation control panel
Analog Inputs 12 x 4 to 20 mA
Modbus Inputs Up to 87 addressable sensors on 3 RS-485 channels (29 each)
Sensor Types CO, NO2, EX, NH3, H2S, REF, CO2, O2 plus 21 custom
Relays 3 SPDT (Form C), 10 A resistive at 120/240 VAC, pilot duty
Horn/Strobe Outputs 2 x 24 VDC, 250 mA max each
Display Backlit LCD, 2 rows x 16 characters
Buzzer 90 dBA at 1 ft
Electrical
Power Supply 90 to 250 VAC, 1 A, 47 to 63 Hz, single phase
Fuse 1 A, 250 V, 5 x 20 mm slow blow
Sensor Wiring 500 ft (18 AWG), 800 ft (16 AWG), 1,250 ft (14 AWG) max
Modbus Wiring Trunk up to 1,000 m (3,281 ft) at 9600 baud (AWG 26 or wider); Cat 5 up to 600 m (1,968 ft)
Physical
Dimensions 10.5 x 12.5 x 2 in (267 x 318 x 51 mm)
Weight 6.5 lb (2.9 kg)
Enclosure NEMA 1, lockable
Environmental
Operating Temperature 0°C to 40°C (32°F to 104°F)
Humidity 0 to 95% RH, non-condensing
Listings and Approvals
Agency Approvals ETL Listed to UL 508A
Approval Details ETL Listed to UL 508A and CAN/CSA C22.2 No. 14-13