Macurco DVP-120M Detection and Ventilation Control Panel, 12 Analog Inputs, Modbus
- Part number / SKU
- DVP-120M
- Detection and ventilation panel
- ETL Listed to UL 508A
Works with: Macurco 6-Series gas detectors (via MRS-485 adapter), MRS-485 Modbus adapter, DVP-485 Modbus adapter, Macurco 4 to 20 mA gas transducers, Macurco GD-6 combustible gas detector Confirmed by the manufacturer
In stock
- Warranty
- Manufacturer warranty
Need 5 or more? Request volume pricing
- (305) 357-6575
- 100K+ orders shipped
- 30-day returns
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Mixed sensor inputs
12 analog 4 to 20 mA channels plus up to 87 Modbus sensors.
-
Fan and alarm control
three Form C relays rated 10 A resistive at 120/240 VAC.
-
Local alerts
90 dBA buzzer and two 24 VDC horn/strobe drivers.
-
Wide power input
90 to 250 VAC, 47 to 63 Hz.
Specifications
Technical specifications
| Product identifiers | |
|---|---|
| SKU | DVP-120M |
| General | |
| Brand | Macurco |
| Model | DVP-120M |
| Device Type | Detection and ventilation panel |
| Device Type Detail | Detection and ventilation control panel |
| Analog Inputs | 12 x 4 to 20 mA |
| Modbus Inputs | Up to 87 addressable sensors on 3 RS-485 channels (29 each) |
| Sensor Types | CO, NO2, EX, NH3, H2S, REF, CO2, O2 plus 21 custom |
| Relays | 3 SPDT (Form C), 10 A resistive at 120/240 VAC, pilot duty |
| Horn/Strobe Outputs | 2 x 24 VDC, 250 mA max each |
| Display | Backlit LCD, 2 rows x 16 characters |
| Buzzer | 90 dBA at 1 ft |
| Electrical | |
| Power Supply | 90 to 250 VAC, 1 A, 47 to 63 Hz, single phase |
| Fuse | 1 A, 250 V, 5 x 20 mm slow blow |
| Sensor Wiring | 500 ft (18 AWG), 800 ft (16 AWG), 1,250 ft (14 AWG) max |
| Modbus Wiring | Trunk up to 1,000 m (3,281 ft) at 9600 baud (AWG 26 or wider); Cat 5 up to 600 m (1,968 ft) |
| Physical | |
| Dimensions | 10.5 x 12.5 x 2 in (267 x 318 x 51 mm) |
| Weight | 6.5 lb (2.9 kg) |
| Enclosure | NEMA 1, lockable |
| Environmental | |
| Operating Temperature | 0°C to 40°C (32°F to 104°F) |
| Humidity | 0 to 95% RH, non-condensing |
| Listings and Approvals | |
| Agency Approvals | ETL Listed to UL 508A |
| Approval Details | ETL Listed to UL 508A and CAN/CSA C22.2 No. 14-13 |