Macurco · Fire Alarm

Macurco GD-2A Combustible Gas Detector for Methane and Propane, 12 to 24 VAC/VDC

Part number / SKU
GD-2A
  • Combustible gas detector
  • Methane and propane
  • Surface
  • 12 to 24 VAC or VDC
  • UL 2075

$205.99

In stock

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing
  • Help in English, Spanish and Portuguese

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Macurco GD-2A is a combustible gas detector that senses methane (natural gas) and propane (LP gas) and signals a connected alarm panel through relay outputs. Its alarm set point is 25% LEL per UL 1484, and it does not detect carbon monoxide.

It runs on 12 to 24 VAC or VDC, drawing 22 mA at 24 VDC in normal operation and 35 mA at 24 VDC in alarm. An SPDT alarm relay (0.125 A, 40 V, 3 VA) and a normally closed trouble relay (0.250 A, 40 V, 10 VA) connect to the panel. The self-purging semiconductor sensor needs no maintenance, and the white three-part case surface mounts or fits over a 4 in square or double gang box. It is listed to UL 2075.

  • Best for: connecting natural gas and propane detection to an alarm panel.
  • System fit: security and alarm panels with 12 to 24 V auxiliary power and relay zone inputs.
  • Important to know: it has no built-in sounder; connect a UL listed audible device of at least 85 dB as Macurco requires.

Why teams choose it

Built for fire alarm systems

  • Two gases

    detects methane (natural gas) and propane (LP).

  • Panel ready

    SPDT alarm relay and normally closed trouble relay.

  • Low current

    22 mA at 24 VDC in normal operation.

  • UL 2075 listed

    sensitivity tested per UL 1484 at 25% LEL.

Specifications

Technical specifications

Ask about a spec
Product identifiers
SKUGD-2A
General
Brand Macurco
Model GD-2A
Device Type Combustible gas detector
Detection Type Methane and propane
Detection Type Detail Natural gas; LP
Sensor Self-purging semiconductor
Alarm Set Point 25% LEL (per UL 1484)
Mount Type Surface
Mount Type Detail Or over a 4 in square or double gang box
Electrical
Operating Voltage 12 to 24 VAC or VDC
Standby Current 45 mA at 12 VDC; 22 mA at 24 VDC; 65 mA at 12 VAC; 45 mA at 24 VAC
Alarm Current 70 mA at 12 VDC; 35 mA at 24 VDC; 100 mA at 12 VAC; 65 mA at 24 VAC
Power Consumption About 0.75 W normal; 1.0 W in alarm
Alarm Relay SPDT, 0.125 A, 40 V, 3 VA
Trouble Relay Normally closed, 0.250 A, 40 V, 10 VA
Physical
Dimensions 4.5 x 5 x 1.625 in
Weight 0.54 lb
Color White
Environmental
Operating Temperature 32°F to 120°F (0°C to 49°C)
Listings and Approvals
Agency Approvals UL 2075
Standards Sensitivity tested per UL 1484

Security projects · South Florida