Macurco GD-6 Combustible Gas Detector, Controller and Transducer, 4 to 20 mA
- Part number / SKU
- GD-6
- Combustible gas detector
- Methane, propane or hydrogen
- Standard 4 x 4 electrical box
- 12 to 24 VAC or 12 to 48 VDC
- ETL Listed to UL 61010-1
Works with: Macurco DVP-120 control panel, GDM-FCK methane field calibration kit, GDP-FCK propane field calibration kit, GDH-FCK hydrogen field calibration kit Confirmed by the manufacturer
In stock
- Warranty
- Manufacturer warranty
Need 5 or more? Request volume pricing
- (305) 357-6575
- 100K+ orders shipped
- 30-day returns
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Three selectable gases
methane, propane or hydrogen.
-
Built-in control
fan relay and alarm relay with adjustable set points.
-
4 to 20 mA output
reports 0 to 50% LEL to a controller.
-
End-of-life signal
alerts five years after installation.
Specifications
Technical specifications
| Product identifiers | |
|---|---|
| SKU | GD-6 |
| General | |
| Brand | Macurco |
| Model | GD-6 |
| Device Type | Combustible gas detector |
| Device Type Detail | Controller and transducer |
| Detection Type | Methane, propane or hydrogen |
| Detection Type Detail | Selectable |
| Sensor | Pellistor (catalytic bead), non-replaceable, 5+ year life |
| Range | 0 to 50% LEL |
| Coverage | About 900 sq ft (84 sq m), depending on air movement |
| Analog Output | 4 to 20 mA (0 to 50% LEL); 24 mA on fault |
| Fan Relay | 5 A, 240 VAC, SPDT, pilot duty; 3 to 20% LEL (default 10%); latching or non-latching |
| Alarm Relay | 0.5 A, 120 V, 60 VA; NO or NC; 5 to 25% LEL (default 20%) |
| Buzzer | 85 dBA at 10 cm (off by default) |
| Display | 3-digit LED (off by default) |
| Mount Type | Standard 4 x 4 electrical box |
| Electrical | |
| Operating Voltage | 12 to 24 VAC or 12 to 48 VDC |
| Power Consumption | 3 W max |
| Current Draw | 23 mA standby; 50 mA fan relay on; 75 mA both relays on (24 VDC) |
| Physical | |
| Dimensions | 4.5 x 4 x 2.125 in |
| Weight | 1 lb (0.45 kg) |
| Color | Dark gray |
| Environmental | |
| Operating Temperature | 0°F to 125°F (-18°C to 52°C) |
| Humidity | 10 to 90% RH, non-condensing |
| Listings and Approvals | |
| Agency Approvals | ETL Listed to UL 61010-1 |
| Approval Details | ETL Listed to UL 61010-1 and CAN/CSA C22.2 No 61010-1 |