Notifier · Fire Alarm

Notifier FCO-951 IntelliQuad PLUS Addressable Multi-Criteria Fire/CO Detector, White

Part number / SKU
FCO-951
  • Multi-criteria fire/CO detector
  • Photoelectric, CO, thermal, IR
  • Addressable, one SLC address
  • Plug-in head for separate base
  • 15 to 32 VDC

Works with: B200S-WH intelligent sounder base, B200S-LF-WH low-frequency sounder base, B501-WHITE 4 in base, B300-6 6 in flanged base, B224BI-WH isolator base, B224RB-WH relay base and 6 more models Confirmed by the manufacturer


$196.70

Special order· Lead time confirmed by our team after you order.

Warranty
Manufacturer warranty

Need project or contract pricing?

Request project pricing
  • Help in English, Spanish and Portuguese

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Notifier FCO-951 is an IntelliQuad PLUS plug-in, addressable multi-criteria fire and carbon monoxide detector. It combines four sensing elements in one unit: photoelectric smoke, an electrochemical CO cell, thermal (135°F fixed plus rate-of-rise) and infrared, and it sends a separate life-safety CO signal while using one SLC address.

The detector runs from 15 to 32 VDC, draws 200 µA in standby and 2 mA in alarm at 24 VDC, and is rated for 32°F to 100°F, 15% to 90% RH and air velocity up to 4000 ft/min. The CO cell has a 10-year life with an end-of-life warning, and smoke and CO sensors use automatic drift compensation. It is listed to UL 268 7th Edition, UL 521 and UL 2075.

Notifier recommends the B200S Series intelligent sounder bases, which sound Temporal 3 for fire and Temporal 4 for CO. Other bases include the B501 4 in base, the B300-6 6 in flanged base, the B224BI isolator base and the B224RB relay base.

  • Best for: addressable sites that need combined smoke, heat and system-connected CO detection from one device and one address.
  • System fit: Notifier FlashScan fire alarm systems; B200S, B501, B300-6, B224BI and B224RB bases.
  • Important to know: the detector plugs into a separate base that is ordered as its own part, and the CO cell has a 10-year life; installation and programming must be done by a qualified fire alarm technician in line with local code and the panel manufacturer's instructions.

Why teams choose it

Built for fire alarm systems

  • Four sensors in one

    photoelectric, CO, thermal and infrared sensing combined in a single head.

  • Separate CO signal

    reports carbon monoxide apart from fire, with distinct Temporal 3 and Temporal 4 tones on B200S bases.

  • 10-year CO cell

    built-in end-of-life warning for the CO sensor.

  • Nuisance rejection

    designed to reject certain nuisance sources such as theater smoke.

Specifications

Technical specifications

Ask about a spec
Product identifiers
SKUFCO-951
General
Brand Notifier
Series IntelliQuad PLUS
Model FCO-951
Device Type Multi-criteria fire/CO detector
Device Type Detail Addressable
Detection Type Photoelectric, CO, thermal, IR
Detection Type Detail Electrochemical CO, thermal (135°F fixed and rate-of-rise), infrared
Addressing Addressable, one SLC address
Protocol FlashScan
CO Alarm Thresholds 70 ±5 ppm in 60 to 240 min; 150 ±5 ppm in 10 to 50 min; 400 ±10 ppm in 4 to 15 min
CO Cell Life 10 years with end-of-life warning
Testing RealTest CO testing capability
Color White
Electrical
Operating Voltage 15 to 32 VDC
Standby Current 200 µA at 24 VDC (one communication every 5 seconds, green LED blinking)
Alarm Current 2 mA at 24 VDC (red LED solid)
Maximum Current 4.5 mA at 24 VDC (amber LED solid)
Isolator Load Rating 0.0063
Physical
Mount Type Plug-in head for separate base
Height in B200S Base 2.7 in (69 mm)
Diameter in B200S Base 6.875 in (175 mm)
Weight 3.4 oz (95 g)
Environmental
Operating Temperature 32°F to 100°F (0°C to 38°C)
Relative Humidity 15% to 90% non-condensing
Air Velocity 0 to 4000 ft/min (0 to 1219.2 m/min)
Listings and Approvals
Agency Approvals UL/ULC Listed S1111; CSFM 7272-0028:0510
Standards UL 268 7th Edition; UL 521; UL 2075 (system-connected life-safety CO); CO sensitivity tested to UL 2034 limits

Security projects · South Florida

Planning a fire alarm, access or camera project?

Send the site details and our team helps with product selection, a site survey and a project quote.

Start a project request