Notifier · Fire Alarm

Notifier FS-OSI-RI Intelligent Reflective Imaging Beam Smoke Detector with Reflector

Part number / SKU
FS-OSI-RI
  • Imaging beam smoke detector
  • Infrared light obscuration
  • Addressable
  • 24 VDC nominal
  • UL, FM, CSFM

Works with: NFW-50X, NFW-100X, NFS-320, NFS2-640, NFS2-3030, BEAMHKR reflector heater kit and 3 more models Confirmed by the manufacturer


$849.46

Special order· Lead time confirmed by our team after you order.

Need project or contract pricing?

Request project pricing
  • Help in English, Spanish and Portuguese

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Notifier FS-OSI-RI is an intelligent single-ended reflective imaging beam smoke detector that combines the transmitter and receiver in one unit and includes a reflector. It uses infrared light obscuration: the beam travels to the reflector, and smoke-related changes in received signal strength trigger alarms. Notifier lists it for large open areas with high ceilings, such as warehouses, atriums, aircraft hangars, sports arenas and concert halls.

Protection range is 16 to 328 ft (5 to 100 m), with 30 to 60 ft between beams on smooth ceilings. The detector runs on 24 VDC nominal (15 to 32 VDC), draws 14 mA standby at 24 VDC, and tolerates building movement of plus or minus 1 degree. Four sensitivity levels from 25% to 50% are set automatically from the measured reflector size, with automatic drift compensation.

It works with the NFW-50X, NFW-100X, NFS-320, NFS2-640 and NFS2-3030 in FlashScan or CLIP mode. Options include the BEAMHKR reflector heater kit, the RTS151 remote test station, the OSP-002 laser alignment tool and the OSP-004 test filter pack.

  • Best for: warehouses, atriums, aircraft hangars, sports arenas and concert halls with large open areas and high ceilings.
  • System fit: Notifier NFW-50X, NFW-100X, NFS-320, NFS2-640 and NFS2-3030 panels in FlashScan or CLIP mode.
  • Important to know: up to 4 detectors per loop on a dedicated circuit on Notifier panels; installation and programming must be done by a qualified fire alarm technician in line with local code and the panel manufacturer's instructions.

Why teams choose it

Built for fire alarm systems

  • Long range

    protects 16 to 328 ft from one transceiver and reflector.

  • Auto sensitivity

    four levels from 25% to 50% set from the measured reflector size.

  • Movement tolerance

    allows plus or minus 1 degree of building movement, with 20 degree vertical and 50 degree horizontal alignment adjustment.

  • Remote testing

    works with the UL listed RTS151 remote test station.

Specifications

Technical specifications

Ask about a spec
Product identifiers
SKUFS-OSI-RI
General
Brand Notifier
Model FS-OSI-RI
Device Type Imaging beam smoke detector
Device Type Detail Intelligent single-ended reflective; includes reflector
Detection Type Infrared light obscuration
Addressing Addressable
Protocol FlashScan or CLIP
Coverage 16 to 328 ft (5 to 100 m)
Beam Spacing 30 to 60 ft between beams on smooth ceilings
Field of View 12 degrees
Alignment Adjustment 20 degrees vertical, 50 degrees horizontal
Movement Tolerance Plus or minus 1 degree
Sensitivity Level 1 25%, level 2 30%, level 3 40%, level 4 50%; set automatically from reflector size
Devices per Loop Up to 4 per loop on a dedicated circuit (Notifier panels)
Electrical
Operating Voltage 24 VDC nominal
Operating Voltage Detail 15 VDC min, 32 VDC max
Standby Current 13 mA at 32 VDC; 14 mA at 24 VDC; 20 mA at 15 VDC
Alarm Current 22 mA at 32 VDC; 15 mA at 24 VDC; 22 mA at 15 VDC (LED on)
Terminals Removable plug-in terminal blocks, 14 AWG (2.08 mm²)
Physical
Detector Dimensions 6 in H x 10 in W x 4.5 in D (152.4 x 254 x 114.3 mm)
Reflector Dimensions 9.06 in H x 7.87 in W (230 x 200 mm)
Weight 2.48 lb (1.12 kg) installed
Housing Paintable
Environmental
Operating Temperature 32°F to 100°F (0°C to 37.8°C) UL listed; application range -4°F to 131°F (-20°C to 55°C)
Relative Humidity 0% to 95% non-condensing
Listings and Approvals
Agency Approvals UL, FM, CSFM
Approval Details UL Listed; FM PR449231; CSFM 7260-0028:0509

Security projects · South Florida