Notifier FS-OSI-RI Intelligent Reflective Imaging Beam Smoke Detector with Reflector
- Part number / SKU
- FS-OSI-RI
- Imaging beam smoke detector
- Infrared light obscuration
- Addressable
- 24 VDC nominal
- UL, FM, CSFM
Works with: NFW-50X, NFW-100X, NFS-320, NFS2-640, NFS2-3030, BEAMHKR reflector heater kit and 3 more models Confirmed by the manufacturer
Special order· Lead time confirmed by our team after you order.
Need 5 or more? Request volume pricing
- (305) 357-6575
- 100K+ orders shipped
- 30-day returns
Need project or contract pricing?
Request project pricing- Help in English, Spanish and Portuguese
Not sure it fits your system? Check compatibility
Overview
What it is and who it is for
Why teams choose it
Built for fire alarm systems
-
Long range
protects 16 to 328 ft from one transceiver and reflector.
-
Auto sensitivity
four levels from 25% to 50% set from the measured reflector size.
-
Movement tolerance
allows plus or minus 1 degree of building movement, with 20 degree vertical and 50 degree horizontal alignment adjustment.
-
Remote testing
works with the UL listed RTS151 remote test station.
Specifications
Technical specifications
| Product identifiers | |
|---|---|
| SKU | FS-OSI-RI |
| General | |
| Brand | Notifier |
| Model | FS-OSI-RI |
| Device Type | Imaging beam smoke detector |
| Device Type Detail | Intelligent single-ended reflective; includes reflector |
| Detection Type | Infrared light obscuration |
| Addressing | Addressable |
| Protocol | FlashScan or CLIP |
| Coverage | 16 to 328 ft (5 to 100 m) |
| Beam Spacing | 30 to 60 ft between beams on smooth ceilings |
| Field of View | 12 degrees |
| Alignment Adjustment | 20 degrees vertical, 50 degrees horizontal |
| Movement Tolerance | Plus or minus 1 degree |
| Sensitivity | Level 1 25%, level 2 30%, level 3 40%, level 4 50%; set automatically from reflector size |
| Devices per Loop | Up to 4 per loop on a dedicated circuit (Notifier panels) |
| Electrical | |
| Operating Voltage | 24 VDC nominal |
| Operating Voltage Detail | 15 VDC min, 32 VDC max |
| Standby Current | 13 mA at 32 VDC; 14 mA at 24 VDC; 20 mA at 15 VDC |
| Alarm Current | 22 mA at 32 VDC; 15 mA at 24 VDC; 22 mA at 15 VDC (LED on) |
| Terminals | Removable plug-in terminal blocks, 14 AWG (2.08 mm²) |
| Physical | |
| Detector Dimensions | 6 in H x 10 in W x 4.5 in D (152.4 x 254 x 114.3 mm) |
| Reflector Dimensions | 9.06 in H x 7.87 in W (230 x 200 mm) |
| Weight | 2.48 lb (1.12 kg) installed |
| Housing | Paintable |
| Environmental | |
| Operating Temperature | 32°F to 100°F (0°C to 37.8°C) UL listed; application range -4°F to 131°F (-20°C to 55°C) |
| Relative Humidity | 0% to 95% non-condensing |
| Listings and Approvals | |
| Agency Approvals | UL, FM, CSFM |
| Approval Details | UL Listed; FM PR449231; CSFM 7260-0028:0509 |