Notifier · Fire Alarm

Notifier KDM-R2 80-Character Keypad Display Module

Part number / SKU
KDM-R2
  • Keypad display module
  • Top row of the cabinet

Works with: NFS2-640 (CPU2-640 / CPU2-640E), BMP-1 blank module, DP-DISP2 mounting plate, NCA-2 network control annunciator, NCS/ONYXWorks network display Confirmed by the manufacturer


$1,058.58

Special order· Lead time confirmed by our team after you order.

Need project or contract pricing?

Request project pricing
  • Help in English, Spanish and Portuguese

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Notifier KDM-R2 is an 80-character backlit LCD keypad display module with a QWERTY programming and control keypad. Notifier lists it as required for each stand-alone 80-character display system, and in the NFS2-640 product line it is one of the two display options for single CPU systems, alongside the NCA-2.

The 2 x 40 character display uses a long-life LED backlight, and the keypad provides Acknowledge/Scroll Display, Signal Silence, Drill, System Reset and Lamp Test controls with 12 status LEDs. It requires the top row of the cabinet, with two BMP-1 blank modules and a DP-DISP2 mounting plate ordered separately. In network nodes it shows local node information, while network information needs an NCA-2 or NCS/ONYXWorks display.

  • Best for: local display and programming of Notifier NFS2-640 systems and network nodes.
  • System fit: Notifier NFS2-640 (CPU2-640) systems and network nodes; network display requires NCA-2 or NCS/ONYXWorks.
  • Important to know: it mounts in the top cabinet row and the BMP-1 blanks and DP-DISP2 plate are ordered separately; installation and programming must be done by a qualified fire alarm technician in line with local code and the panel manufacturer's instructions.

Why teams choose it

Built for fire alarm systems

  • Full keypad

    QWERTY keypad for programming and control at the panel.

  • Readable display

    80-character, 2 x 40 LCD with long-life LED backlight.

  • Status at a glance

    12 LEDs including fire alarm, supervisory, trouble and releasing (abort, pre-discharge, discharge).

  • Network node use

    displays local node information in networked systems.

Specifications

Technical specifications

Ask about a spec
Product identifiers
SKUKDM-R2
General
Brand Notifier
Model KDM-R2
Device Type Keypad display module
Display 80 characters (2 x 40) LCD with long-life LED backlight
Program Keypad QWERTY type
Keypad Controls Acknowledge/Scroll Display; Signal Silence; Drill; System Reset; Lamp Test
Indicators 12 LEDs: Power, Fire Alarm, Pre-Alarm, Security, Supervisory, System Trouble, Signals Silenced, Points Disabled, Control Active, Abort, Pre-Discharge, Discharge
Mount Type Top row of the cabinet
Mounting Hardware Two BMP-1 blank modules and DP-DISP2 mounting plate, ordered separately
Network Use Shows local node information; network display needs an NCA-2 or NCS/ONYXWorks

Security projects · South Florida

Planning a fire alarm, access or camera project?

Send the site details and our team helps with product selection, a site survey and a project quote.