Notifier · Fire Alarm

Notifier NBG-12 Dual Action Conventional Manual Fire Alarm Pull Station, Red

Part number / SKU
NBG-12
  • Fire alarm pull station
  • Conventional
  • Surface mount
  • UL, cUL, CSFM, FM, MEA

Works with: SFP Series conventional fire alarm control panels, XP Series transponders, SB-10 surface back box, SB-I/O surface back box, BG12TR trim ring Confirmed by the manufacturer


$51.99

Special order· Lead time confirmed by our team after you order.

Free Economy shipping available at checkout

Need project or contract pricing?

Request project pricing
  • Help in English, Spanish and Portuguese

Not sure it fits your system? Check compatibility

Overview

What it is and who it is for

The Notifier NBG-12 is a non-coded, dual action manual pull station from the NBG-12 Series, molded in red Lexan polycarbonate. It gives a normally open alarm input to conventional fire alarm control panels such as the SFP Series and to Notifier XP transponders.

The push-in, pull-down handle latches when operated and shows ACTIVATED in yellow, and the pull force stays within the ADA 5 lb maximum. Field wiring lands on a four-position terminal strip with captive 8/32 screws that accepts up to 12 AWG. The station surface mounts on an SB-10 or SB-I/O back box or semi-flush mounts to a single-gang, double-gang or 4 in square box, with the BG12TR trim ring as an option.

Notifier lists the NBG-12 with UL file S692, CSFM 7150-0028:199, FM approval, MEA 67-02-E and Lloyd's Register type approval, plus U.S. Coast Guard approvals with the AFP-200, NFS-640 and AFP1010/AM2020 panels.

  • Best for: manual fire alarm initiation on conventional fire alarm systems and XP transponder inputs.
  • System fit: conventional fire alarm control panels such as the Notifier SFP Series, and Notifier XP transponders (normally open IDC input).
  • Important to know: installation and programming must be done by a qualified fire alarm technician per local code.

Why teams choose it

Built for fire alarm systems

  • Clear activation

    the handle latches down and shows ACTIVATED in yellow so the operated station can be found.

  • Easy to operate

    pull force stays within the ADA 5 lb maximum.

  • Service without false alarms

    the station opens for inspection without initiating an alarm.

  • Flexible mounting

    surface mount on SB-10 or SB-I/O, or semi-flush to single-gang, double-gang or 4 in square boxes.

Specifications

Technical specifications

Ask about a spec
Product identifiers
SKUNBG-12
General
Brand Notifier
Model NBG-12
Series NBG-12 Series
Device Type Fire alarm pull station
Device Type Detail Dual action manual
Addressing Conventional
Coding Non-coded
Operation Push in, pull down; handle latches down and shows ACTIVATED in yellow
Markings Braille text on the finger-hold area and the top of the handle; white arrows show direction of operation
Pull Force Within the ADA 5 lb maximum
Inspection Opens for inspection without initiating an alarm; product ID label visible with the cover open
Electrical
Contacts Normally open
Terminals Four-position terminal strip molded into the backplate, captive Phillips combination-head 8/32 screws
Wire Size Up to 12 AWG (3.1 mm2)
Circuit Initiating device circuit (IDC) input to conventional FACPs and XP transponders
Physical
Housing Material Lexan (polycarbonate)
Color Red
Mount Type Surface mount
Mount Type Detail On SB-10 or SB-I/O back box, semi-flush to a single-gang, double-gang or 4 in (10.16 cm) square electrical box
Single-Gang Overlap Backplate overlaps a single-gang cutout by 0.5 in (1.27 cm)
Trim Ring BG12TR (optional)
Packaging Clear PVC clamshell with a station-shaped dust and paint cover
Listings and Approvals
Agency Approvals UL, cUL, CSFM, FM, MEA
Approval Details UL and cUL Listed S692; CSFM 7150-0028:199; FM Approved; MEA 67-02-E; Lloyd's Register 93/60141 (E3)
U.S. Coast Guard 161.002/23/3 with AFP-200; 161.002/42/1 with NFS-640; 161.002/27/3 with AFP1010/AM2020
Standards UL 38, Manually Actuated Signaling Boxes

Security projects · South Florida